If you fully open the bypass, pretty much all the water will go through it. What you probably want is a Throtling Control Valve (TCV) in the bypass. You will need to set up some control statements so that as the flow in P-42 increases, the TCV will gradually open. You'll need some trial and error to get the settings right. I suggest a butterfly valve type.