Mark,

Thanks again for your advice.

After removing the junction with negative flow and changing the initial setting of FCV to closed, FCV started to open and closed at longer cycle (> 24 hurs), instead of open and close every several hours.  First, I thought FCV started to close at right time between midnight and 6 am most of the time. However, when I adjusted other settings such as HSP pump controls and FCV flow rate, FCV does not close at mid night any more.

By trying different sets of controls, I found the followings:

1. FCV is controled by two control settings (The Clock Time does not seem to have any effect):

    - IF Clock Time  > 6:00 AM  And Clock Time  < 11:59 PM  And R-2MG Hydraulic Grade < 829.00 ft

      THEN FCV-4 FCV Setting = 2,500 gpm

    - IF R-2MG Hydraulic Grade >= 832.99 ft THEN FCV-4 FCV Status = Closed

2. The following control to close FCV does not seem to have any effect.

   - IF Clock Time  >= 11:59 PM  And Clock Time  <= 6:00 AM  THEN FCV-4 FCV Status = Closed

3. FCV pattern which was set according to your last advice also does not seem to have any effect.

With your advice, I now can close FCV according to its elevation, but not according to time.

I'd appreciate your further guidance on how to close the FCV according to time.

Thanks.

Yoko