Applies To Product(s): Bentley SCADAConnect Version(s): 08.11.xx.xx Environment: N/A Area: Data Source Connection Subarea: Citect Original Author: Akshaya Niraula, Bentley Technical Support Group Problem Description Getting an error message like below when using/testing the Citect datasource: --------------------------- SCADAConnect Message --------------------------- Citect ctAPI dlls are missing. Please copy the required ctAPI dlls into the WaterGEMS installation folder. --------------------------- OK --------------------------- Reason There are some dll (assembly) files needed to use the Citect DataSouce in SCADAConnect and they need to be at the same location where WaterGEMS/WaterCAD/HAMMER is running. Steps to Resolve Please make sure you have following dll files in the directory where the product is running (generally C:\Program Files (x86)\Bentley\WaterGEMS or WaterCAD or HAMMER\) . Version 7 (or 6) of Citect needs: CiDebugHelp.dll CtApi.dll CtEng32.dll Ctg32.dll CtRes32.DLL CtUtil32.dll Ct_ipc.dll The above listed files can be obtained from the computer where Citect is installed. Pleae copy/ these files to the directory from where software (WaterGEMS, WaterCAD, HAMMER) is running. If you couldn't obtain the files listed above, please contact Technical Support Group. See Also http://communities.bentley.com/products/hydraulics___hydrology/w/hydraulics_and_hydrology__wiki/could-not-establish-scada-connection-scadaconnect-citect.aspx
↧