Applies To Product(s): HAMMER Version(s): 10.00.xx.xx, 08.11.xx.xx Area: Modeling Original Author: Jesse Dringoli, Bentley Technical Support Group Problem In the Transient tab of a pump definition, there are several default selections available for Specific Speed. What is the source of the 4-quadrant characteristic curves behind these specific speeds? Also - what is the source of the curves behind the default Specific Speeds for turbines Solution Pumps For Pumps, the specific speeds 25, 94 and 145 (SI units) were derived from data published by Stepanoff (1957), as well as personal correspondance, in terms of relative Q and N along lines of constant head and torque throughout the entire operating range. The other default specific speeds are from Thorley, A.R.D and A. Chaudry., "Pump Characteristics for Transient Flow Analysis", Department of Mechnical Engineering & Aeronautics, City University, London ECIV OHB Turbines For turbines, the specific speeds 115, 170 and 230 (SI units) are from published data from the US Bureau of Reclamation (USBR).
↧